Features• Large display shows preset value and running batch value simultaneously.• The analog output value reflects the course of the batch process; fourteen different profiles can be selected.• Two-stage control for batching larger quantities.• Self-learning overrun correction.• Easy operation to enter a batch value and to control the process.• Count-up and count-down function available.• Scaled pulse output reflecting accumulated or batched total.• Actual batched quantity: seven 17mm (0.67") digits.• Preset value: seven 17mm (0.67") digits during programming and 8mm (0.31") digits during batchprocess.• Total - resettable: seven 17mm (0.67") digits.• Accumulated total - not resettable: eleven 8mm (0.31") digits.• Green LED backlight.• Auto backup of settings and running totals in EEPROM memory.• Operational temperature: -30°C to +80°C (-22°F to 178°F).• Very compact design for panel mount, wall mount or field mount applications.• Rugged aluminum or GRP field mount enclosure IP67 / NEMA4X.
ApplicationsFor batch applications where re-transmission of the course of the process is required.Alternative basic models: F030, F130, F131.Alternative advanced models: 300-Series.
Flowmeter Inputs• Pulse type inputs:Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), active pulse signal.• (0)4 – 20mA.• 0 – 10V DC.
Status Inputs• Remote control: start.• Remote control: pause / stop.
Pulse Outputs• Function: Scaled pulse output according to accumulated or batched total (e.g. a pulse every 3.25 gallons).Max. frequency: 64Hz.Adjustable pulse length from 8 msec. to 2 seconds.• Type: One passive NPN transistor, active PNP transistor or isolated electro-mechanical relay.• Remark: With pulse output one-stage control only.
Alarm Outputs• None.
Analog Outputs• Function: Re-transmitting the course of the batch process.• Type: One passive isolated, floating or loop powered 4 – 20mA output or one active (0)4 – 20mA or 0 – 10V DC output.
Control Outputs• Function: Control outputs for one- or two-stage batching with active overrun correction.• Type: Two passive NPN transistors, active PNP transistors or isolated electro-mechanical relays.• Remark: With two-stage control no pulse output available.
Power Supply• Battery.• 4 – 20mA Loop-powered.• 8 – 24V AC/DC.• 115 – 230V AC.
Sensor Supply• 3.2, 8.2, 12, 24V DC.
Intrinsically Safe• ATEX: II 1 GD EEx ia IIB/IIC T4 T 100 °C
Explosion Proof• ATEX: II 2 G EEx d IIB T5
CommunicationFunction: All process data and settings can be read / modified through the communication link as well as a batch can be started / stopped.Protocol: Modbus RTU.Interface: RS232 / RS485 2-wire or 4-wire / TTL.