F-Series: F113

Field mount - Flow rate monitor / totalizer

with high / low alarms, analog and pulse outputs

The F113 is a versatile flow rate indicator / transmitter and totalizer with continuous flow rate monitoring feature. It offers the ability to set two low flow rate and two high flow rate alarm values. If desired, an alarm ignore function can be set up to allow for an incorrect flow rate for a certain period of time. Up to five outputs are available to transmit flow rate, alarm conditions and accumulated total.
The display shows flow rate, total, accumulated total, alarm values, alarm messages and status. On-screen engineering units are easily configured from a comprehensive selection.

Advantages
  • Robust IP66, IP67 (NEMA Type4X) field enclosure. It is so rugged, you can even stand on it!
  • Intrinsically Safe available - ATEX and IECEx approval for gas and dust applications.
  • Programming can be done by your own crew, with the sensible menu-driven structure, saving cost and irritation. Know one, know them all!
  • Very diverse mounting possibilities: walls, pipes, panels or directly onto outdoor sensors.
Application overview F113

Features

  • Flow rate monitoring: four alarm values can be set: low-low, low, high and high-high flow rate alarm.
  • Alarm values can be changed by the operator or they can be password protected.
  • Alarm ignore function allows an incorrect flow rate for a certain period of time.
  • Analog and pulse outputs.
  • Displays total and flow rate simultaneously.
  • Large digit selection for flow rate or total.
  • Flow rate: seven 17mm (0.67") or 8mm (0.31") digits.
  • Total - resettable: seven 17mm (0.67") digits.
  • Accumulated total - not resettable: eleven 8mm (0.31") digits.
  • Separate engineering units for flow rate and total on the display.
  • Up to four configurable alarm or scaled pulse outputs.
  • Displays clear alarm messages.
  • LED backlight.
  • Auto backup of settings and running totals in EEPROM memory.
  • Ambient temperature: -40°C to +80°C (-40°F to 176°F).
  • Remote control input to reset total or to lock the "clear total" button.
  • Various accessories are available for this product.
  • The F-Series is so rugged, even a truck can stand on it!

Flowmeter Inputs

  • Pulse type inputs:
    Reed-switch, open collector, NAMUR, NPN/PNP pulse, Sine wave (coil), active pulse signal.
  • (0)4 – 20mA.
  • 0 – 10V DC.

Status Inputs

  • Remote control: external reset for clearing total or to disable manual clearing through the keypad.

Pulse Outputs

  • Function: Scaled pulse output according to accumulated total (e.g. a pulse every 3.25 gallons).
    Max. frequency: 500Hz.
    Adjustable pulse length from 0.001 sec. to 9.999 seconds.
  • Type: Up to three passive NPN transistors or active PNP transistors or up to four isolated electro-mechanical relays.

Alarm Outputs

  • Function: Configurable alarm outputs for low-low, low, high, high-high or all combined flow rate alarms.
  • Type: Up to three passive NPN transistors or active PNP transistors or up to four isolated electro-mechanical relays.

Analog Outputs

  • Function: Re-transmitting the flow rate - the output can be scaled to any range (e.g. 200 L/min to 1200 L/min).
  • Type: One passive isolated, floating or loop powered 4 – 20mA output or one active (0)4 – 20mA or 0 – 10V DC output.

Applications

  • The F-Series is your first and best choice for field mount indicators in safe and hazardous area applications. Especially in harsh weather conditions like rain, snow, salty atmospheres and temperatures between -40°C up to +80°C (-40°F up to 176°F).
  • Liquid flow measurement where continuous flow rate monitoring is important. Also re-transmission of the flow rate and/or totalizer functions or serial communication is required.
    Alternative basic model: F013. Alternative advanced model: F118 or the D-Series basic DIN panel mount indicators.

Power Supply

  • Long life Lithium battery.
  • 4 – 20mA Loop-powered.
  • 8 – 24V AC/DC.
  • 115 – 230V AC.
  • Basic: 8 - 30V DC.

Sensor Supply

  • 3.2, 8.2, 12, 24V DC.

Intrinsically Safe

  • ATEX:
    II 1 G Ex ia IIB/IIC T4 Ga
    II 1 D Ex ia IIIC T100 °C Da
  • IECEx:
    Ex ia IIC/IIB T4 Ga
    Ex ia IIIC T100 °C Da

Explosion Proof

  • ATEX:
    II 2 G / Ex d IIB T5 Gb
    II 2 D / Ex t IIIB T100°C Db

Communication
Function: All process data and settings can be read and modified through the communication link.
Protocol: Modbus ASCII / RTU.
Interface: RS232 / RS485 2-wire or 4-wire / TTL.
– HART communication is available with the F018 Flow rate Monitor / Totalizer.

LCD example F113
Photo F113